CIBOLO
STANDARD
OPERATING PROCEDURES
SELF CONTAINED BREATHING APPARATUS
(SCBA)
1.
Personnel will use SCBA’s at all alarms where smoke is visible or where
there is ANY possibility that Toxic Gases, Dust or any other respiratory danger
might exist.
2.
Personnel utilizing SCBA’s will operate in teams of two (2) or more.
3.
No Engine Company will respond to any alarm unless it carries at least
one (1) SCBA for each person responding on that unit. The SCBA will be in easy reach of each person
operating on that unit except the Driver.
The Driver will have an SCBA available; however, it can be located in a
compartment.
4.
When SCBA’s are utilized, they are to be utilized in full compliance of
the Manufacturers Operating Instructions.
5.
All components, such as straps and belts, are to be fastened in
place. Waist belts are NOT to be
altered, left loose or folded away. They
must be in place and worn.
6.
Nomex hoods will be worn outside the face piece sealing. Wearing Nomex hood between the face piece
seal and the skin could cause leakage in the face piece and place the user in
danger.
7.
All personnel are to assure that facial hair does not interfere with
face piece sealing. Regulations on
facial hair for fire operations personnel are as follows:
1.
No Beards will be allowed.
2.
Sideburns are to be kept trim to the point where they are not dense or
thick where they prevent proper face piece sealing.
3.
Mustaches will be allowed as long as they do not interfere with face
piece sealing.
4.
Excessive head hair will not be allowed if it interferes with face
piece sealing or proper operation of face piece straps.
5.
Eyeglasses are not to be worn when using SCBA’s.
8.
SCBA’s are to be used during overhaul operations in accordance with the
department’s Incident Command System.
INSPECTION:
1.
All SCBA’s utilized in the Fire Department will comply with state law
in regards to types purchased, tests, inspections, etc.
2.
Each SCBA will be thoroughly inspected monthly. A
3.
Each SCBA will be inspected daily by personnel assigned to that
unit. Any malfunctions, problems, etc.
with any SCBA will be noted in the Department Daily Inspection and Maintenance
log book and reported to the Lieutenant or shift leader.
4.
Each spare cylinder will be inspected daily by the personnel assigned
to the unit which carries spare cylinders.
Any malfunctions, problems, etc. with any SCBA will be noted in the Cibolo
Fire Department SCBA Daily Inspection and Maintenance log book and reported to
the Lieutenant.
5.
Company Officers or shift leaders will assign personnel to inspect
SCBA’s and spare cylinders on units, which do not have assigned personnel.
6.
Repairs to SCBA’s will be performed only by personnel who are certified
to do so.
7.
Personal Alert Safety System (PASS) devices shall be inspected daily,
at the beginning of each duty cycle, or after each use in accordance with the
manufactures specifications. Batteries
in the PASS device will be changed when the battery indicator shows no less
than one-half full.
AIR
TESTING:
1.
Breathing air produced by the SCBA compressor (Cascade System) will be
tested every four months.
2.
SCBA duty officer will be responsible to assure air testing is
completed on schedule.
3.
SCBA duty officer will monitor air test results and assure all air used
by SCBA’s meets applicable standards.
4.
Every Thursday, the Lieutenant or shift leader will be responsible for
a weekly inspection on Cascade System (air compressor) and any malfunctions,
problems, etc. will be noted in the Air Compressor Log Book.