A.
To provide equipment that will enhance
the safety of every firefighter entering a visually obscured toxic atmosphere
by means on an audible alarm.
All members shall be trained and tested by a certified instructor, recognized by the Texas Commission on Fire Protection, in proper use, selection, care and maintenance of a Personal Alert Safety System (PASS) per NFPA 1982,and HB 382 Section 419.042, and manufacturer specifications through either an integrated on non-integrated PASS system.
A.
PASS
Alarms shall be used in accordance with the following:
1.
The PASS
alarm will be attached to the harness waist belt of the SCBA in easy reach, or
shall be an integrated system as on the Pantherä SCBA models.
The PASS alarm shall be in the “on” position any time a fire fighter
enters a hazardous environment.
B.
Integrated
PASS device systems (Compassä):
a.
The
Pantherä SCBA models are equipped with the Compassä integrated PASS device.
b.
The
1.
Maintenance of
a.
Battery
requirement for the Compassä PASS device, per the manufacturer, is a 9-volt battery.
b.
The
battery is encased in the
c.
The
battery is reached on the back of the
d.
The
battery is to be replaced, per manufacturer, every 1000 hours of use.
e.
To
ease record keeping the battery shall be replaced twice per year, using
daylight savings time as a guide. The
records shall be maintained by the Training Officer, or designee determined by
the Fire Chief.
f.
Instructions
for replacing battery (twice yearly):
1.
Unfasten
2.
3.
Using
an Allen Wrench remove the two screws holding the faceplate for the battery
compartment.
4.
Remove
the faceplate.
5.
Remove
the battery from the Compassä unit and replace with a new battery.
6.
Discard
the battery in an acceptable manner.
g.
Daily
check of unit
1.
Turn
the Compassä unit on by:
2.
Depress
the red button located on the right side of the unit. Listen for an audible alert and visualize
that the lights on the front of the unit are flashing green. Leave the unit on
until it begins to alarm. Turn the unit off by depressing the red button on the
right side of the unit.
3.
Turn
the SCBA cylinder so that it charges the Pantherä SCBA pack system.
Check the Compassä unit turns on automatically when the SCBA pack system is
charged. Listen for an audible alert and
visualize that the lights on the front of the unit are flashing green. Leave the unit on until it begins to
alarm. Depress the red button on the
right side of the unit to reset it.
4.
With
the Compassä unit on depress and hold the red button located
on the right side of the unit until the alarm begins to sound, visualize that
the lights on the front of the unit are red.
5.
After
the alarm has begun to sound and visual check is complete depress the red
button on the right side of the unit to silence the alarm.
6.
Turn
the SCBA cylinder off, and bleed the air from the Pantherä SCBA system by turning the red knob located on
the side of the regulator return the knob to operating position once the system
is purged.
7.
Once
the system is purged depress the red button on the right side of the Compassä unit and turn the unit off.
8.
If any
part of the Compassä unit should be found not to be in working order
remove the SCBA from service and report the discrepancy to the shift officer
(Lieutenant or senior fire fighter) so that they may report the problem to the
Shift Captain.
9.
The
Shift Leader shall report all discrepancies to the Training Officer who shall
correct the problem and return the unit to service as soon as possible.